Automated Logic TS2 Series Thermostats provide reliable temperature control for fan coil units (FCUs) in office buildings, hotels, dorm rooms, and other commercial applications. Available in communicating and non-communicating configurations, these thermostats feature an intuitive touch key interface, built-in temperature sensing, and precise control of fan speed and operating modes.
Designed for 2-pipe and 4-pipe fan coil systems, the TS2 Series supports standalone operation or integration with building automation systems through Modbus RTU communication. Configurable inputs accommodate remote temperature sensors, third-party keycard systems, and equipment interlocks.
Advanced features include 7-day scheduling with four periods per day, economy (ECO) mode, battery-backed settings, built-in diagnostics, and button and menu lockout options. Compatible configurations support permanent split capacitor (PSC) and electronically commutated (EC) fans, with 0–10V or ON/OFF valve control depending on the model.
The TS2 Series helps reduce energy consumption, improve occupant comfort, simplify installation, and support efficient building operations. Modbus-compatible models can integrate with Automated Logic's WebCTRL building automation system.
Key Features & Benefits
Features:
- • Designed for 2-pipe and 4-pipe fan coil units.
- • Available in communicating Modbus RTU and standalone configurations.
- • Intuitive touch key interface with backlit LCD display.
- • Built-in temperature sensor with a measurement range of 0–55°C and accuracy of ±1°C.
- • Supports permanent split capacitor (PSC) and electronically commutated (EC) fan configurations.
- • Supports 3-speed PSC fan control and 0–10V EC fan control, depending on configuration.
- • Supports 0–10V or ON/OFF valve control, depending on model.
- • 7-day and 5+2 scheduling with four periods per day.
- • Economy (ECO) mode for energy-efficient operation.
- • S1/S2 input supports a remote temperature sensor or dry-contact keycard and interlock applications.
- • Keycard input can automatically adjust temperature setpoints based on room occupancy.
- • Battery-backed settings are retained after power outages.
- • Built-in diagnostics provide alarm and fault codes for sensor malfunctions.
- • Button and menu lockout options help prevent unauthorized adjustments.
- • Modbus RTU communication via EIA-485 A/B terminals, with baud rates up to 38,400.
- • Recommended maximum of 25 devices on the communication network.
- • Power supply: 90–240 VAC, 50/60 Hz.
- • Power consumption: less than 2 W.
- • Operating temperature: 0–45°C.
- • Operating humidity: 5–95% RH, non-condensing.
- • PC+ABS flame-retardant enclosure with IP30 rating.
- • Dimensions: 86 × 86 × 11.5 mm.
- • Standard 60 mm wall box mounting.
- • CE compliant.
- • Available in white and black finishes.
Benefits:
- • Energy Savings: Seven-day scheduling, four daily time periods, and ECO mode help optimize energy consumption based on occupancy and operating requirements.
- • Enhanced Comfort: Precise temperature sensing and adjustable fan speeds help maintain comfortable indoor conditions.
- • Flexible System Compatibility: Supports 2-pipe and 4-pipe fan coil units with multiple fan and valve control configurations.
- • Building Automation Integration: Modbus-compatible models integrate with building automation systems, including Automated Logic's WebCTRL platform.
- • Simplified Installation: Standard wall box mounting and configurable input terminals accommodate a variety of installation requirements.
- • Reduced Maintenance: Built-in diagnostics identify sensor malfunctions and provide fault codes to help simplify troubleshooting.
- • Reliable Operation: Battery-backed settings are retained following power outages.
- • Improved Security: Button and menu lockout options help prevent unauthorized changes to thermostat settings.
- • Flexible Occupancy Control: The S1/S2 input supports third-party keycard systems and interlocks for occupancy-based temperature adjustment.
- • Design Flexibility: Available in multiple configurations for 2-pipe and 4-pipe systems, with white or black finishes to suit different applications.