The OptiFlex Integrator (OFHI-A) supports routing between multiple BACnet networks and provides custom control programs for seamless integration with third-party equipment such as variable speed drives, boilers, and lighting systems. It supports multiple industry-standard protocols, including KNX, Modbus TCP/IP, N2 Open, and SNMP. The OFHI-A is also a Google UDMI-compliant gateway and device, providing flexible integration and high-speed network management for the WebCTRL building automation system.
Key Features & Benefits
Features:
- Supports routing between BACnet/IPv6, BACnet/Ethernet, BACnet ARCNET, BACnet MS/TP, and BACnet Secure Connect (SC).
- Includes 1,000 any-protocol integration points and 1,500 BACnet points, expandable to 5,000 total integration points.
- Supports KNX, Modbus TCP/IP, N2 Open, and SNMP protocols through the gigabit Ethernet port.
- Two serial ports support BACnet/ARCNET networks, BACnet MS/TP networks, and Modbus communication.
- Supports up to 254 ARCNET controllers.
- Supports up to 127 MS/TP controllers.
- Can function as a BACnet Broadcast Management Device (BBMD).
- Supports BACnet Foreign Device Registration (FDR).
- Can operate as a Modbus server or client on a Modbus TCP/IP serial network.
- Supports DHCP addressing on IPv4 networks and DHCPv6 and SLAAC addressing on IPv6 networks.
- 10/100/1000 BaseT full-duplex gigabit Ethernet port.
- Ethernet service port provides local access for system startup and troubleshooting.
- Supports network captures for advanced diagnostics.
- Provides network statistics numerically or as trend graphs within WebCTRL.
- Supports up to 999 control programs, depending on available memory.
- Supports up to 12,000 BACnet objects for programming purposes.
- 32-bit ARM Cortex-A8, 600 MHz processor with USB 2.0 host port.
- 8 GB eMMC Flash memory and 512 MB DDR3 DRAM for units manufactured after October 2022.
- Capacitor-backed real-time clock maintains time for up to three days during power failure.
- 35mm DIN rail or screw mounting.
Benefits:
- Simplifies integration between multiple BACnet networks and diverse building automation systems.
- Provides flexible integration with third-party equipment, including variable speed drives, boilers, and lighting systems.
- Supports building expansion with integration capacity expandable to 5,000 total points.
- Enables communication between multiple industry-standard protocols, including KNX, Modbus, N2 Open, and SNMP.
- Allows simultaneous routing and data sharing across a wide range of building subsystems.
- Simplifies BACnet broadcast management and communication across network segments.
- Streamlines integration of third-party BACnet devices through Foreign Device Registration.
- Provides flexible IP network addressing through DHCP, DHCPv6, and SLAAC support.
- Improves troubleshooting through network captures and detailed communication statistics.
- Allows network performance to be monitored through numerical data and trend graphs within WebCTRL.
- Supports customized control strategies to improve building performance and system integration.
- Maintains accurate system time during power outages without requiring a battery.
- Connects seamlessly to the WebCTRL building automation system.
Model: OFHI-A